Chapter 2 Alarm Troubleshooting
Alarm Procedures
The Software Data Integrity Fault alarm occurs when the 15310-CL-CTX card or CTX2500 card exceeds
its flash memory capacity.
Clear the DATAFLT Alarm
Step 1 Complete the “Soft- or Hard-Reset a Controller Card” procedure on page 2-162.
Caution Avoid soft-resetting multiple ONS 15310-MA cards at one time; doing so might cause an unexpected
traffic hit.
Step 2 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447).
2.7.51 DBOSYNC
Default Severity: Major (MJ), Service-Affecting (SA)
Logical Object: NE
The Standby Database Out Of Synchronization alarm applies to the ONS 15310-MA platform and occurs
when the standby CTX2500 card database does not synchronize with the active database on the active
CTX2500 card.
Caution If you reset the active CTX2500 card while this alarm is raised, you will lose current provisioning.
Clear the DBOSYNC Alarm
Step 1 Save a backup copy of the active CTX2500 card database. Refer to the “Maintain the Node” chapter in
the Cisco ONS 15310-CL and Cisco ONS 15310-MA Procedure Guide for procedures.
Step 2 Make a minor provisioning change to the active database to see if applying a provisioning change clears
the alarm:
a. In node view, click the Provisioning > General > General tabs.
b. In the Description field, make a small change such as adding a period to the existing entry.
The change causes a database write but does not affect the node state. The write could take up to a
minute.
Step 3 If the alarm does not clear, log into the Technical Support Website at http://www.cisco.com/techsupport
for more information or call Cisco TAC (1-800-553-2447).
2.7.52 DISCONNECTED
Default Severity: Minor (MN), Non-Service-Affecting (NSA)